Bonding and Grounding for Combustible Dust
How static electricity is kept from igniting dust, what the codes require, and what a static review of your process covers.
Estimate your cost
Bonding and grounding for combustible dust keeps static electricity from building up on conveyors, dust collectors, machines and containers until it discharges as a spark that can ignite a dust cloud. A static review looks at where charge is generated as powders move, which metal parts are bonded together and connected to ground, and where flexible or non-conductive parts need other controls.
What does the fire code require for bonding and grounding?
Canada's national fire code requires the electrically conducting parts of conveying systems, dust collectors, dust-producing machines and any equipment that can accumulate static in a dust atmosphere to be bonded and grounded, with static eliminating devices where needed.
The same section requires cleaning equipment that is electrically conductive and bonded to ground (Article 5.3.1.2) and, in grain handling and storage, conveying equipment belts of static conductive materials (Sentence 5.3.3.2 (2)). Ontario's Fire Code and BC's adopted code carry the same bonding article.
Where can static build up in a dust process?
Static builds up wherever powders and dusts move against equipment, so the gaps a review usually finds sit at unbonded metal parts, flexible connectors, cleaning equipment, bulk containers and non-conductive materials, and five questions cover them.
Is your static control complete? 5 questions
- Are the metal parts of conveyors, dust collectors and dust-producing machines bonded together and grounded?Yes: That is what Sentence 5.3.1.5 (1) of the national fire code requires; the review confirms the connections and their resistance to ground.No: Sentence 5.3.1.5 (1) requires those parts to be bonded and grounded wherever they sit in a dust atmosphere.
- Do flexible connectors, hoses or sleeves sit between bonded metal sections?Yes: NFPA 660’s 2025 edition updates the resistance limits for flexible connectors, so the review checks each one.No: Go to question 3.
- Are vacuums and other cleaning equipment electrically conductive and bonded to ground?Yes: That meets Sentence 5.3.1.2 (1); NFPA 660’s 2025 edition also clarifies bonding and grounding of housekeeping equipment.No: Sentence 5.3.1.2 (1) requires cleaning equipment that is conductive, bonded to ground and does not create static or sparks.
- Do you fill or empty flexible intermediate bulk containers?Yes: NFPA 77’s 2024 edition added a section on these containers; the review covers how each type is used and grounded.No: Go to question 5.
- Are there non-conductive parts or materials where charge can build up?Yes: Sentence 5.3.1.5 (2) requires static accumulation to be prevented by appropriate bonding, grounding and static eliminating devices; NFPA 77 guides the evaluation.No: The review confirms that from the drawings and a site visit.
Based on the National Fire Code of Canada 2020 and the NFPA 77 and NFPA 660 publisher summaries. The engineer confirms the answers for your site.
Who needs a static electricity hazard assessment, and when is it required?
A plant needs a static electricity hazard assessment when powders or dusts are conveyed, collected, mixed or packaged and it is not clear that every conductive part is bonded and grounded, or when a DHA or fire inspection names static as an ignition source. The plastics, rubber and chemicals and pharmaceutical industry pages cover two industries where moving powders are routine.
In British Columbia, once a combustible dust management program is required, section 6.147 (c) of the OHS Regulation requires the risk of electrostatic charge accumulating to be minimized through grounding, bonding or other effective methods, from January 4, 2027.
What does a bonding and grounding review give you?
A bonding and grounding review gives you a list of each item checked, which parts are bonded and grounded, the resistances measured or expected, the gaps found and the changes needed, so maintenance can keep the connections in place.
NFPA 77's 2024 edition guides resistance measurements for bonding connections and total resistance to ground, and adds provisions on powder charge relaxation time and electrostatic ignition risks.
How does a static review differ from a hazardous location classification?
A static review deals with charge built up by moving powders and equipment, while a hazardous location classification zones areas so that installed electrical equipment cannot ignite the dust; both control ignition sources from different directions, and spark detection systems cover hot particles carried along the ducts.
Both often follow from a DHA, which looks at every ignition source in the process, static and electrical equipment included.
What does a review of bonding and grounding for combustible dust cost, and how long does it take?
A static electricity and bonding and grounding review for one process or dust collection system starts at $3,500–$7,500 before HST and typically takes 2–4 weeks from go-ahead, longer where many machines and containers have to be checked.
Every study's starting range is in the cost overview.
Static electricity questions
Is grounding the same as bonding?
Grounding is not the same as bonding: bonding connects conductive parts to each other, and grounding connects them to earth. NFPA 77’s 2024 edition sets out the difference between a grounding conductor, a bonding conductor and an active bond monitoring system.
How often should bonding and grounding be checked?
Bonding and grounding should be checked after any change to equipment, connectors or containers, as well as on a regular inspection schedule. NFPA 77’s 2024 edition gives guidance on resistance measurements for bonding connections and on total resistance to ground.
Does BC require static control for combustible dust?
BC requires the risk of electrostatic charge building up to be minimized through grounding, bonding or other effective methods once a combustible dust management program is needed. Section 6.147 (c) of the OHS Regulation sets that from January 4, 2027.
Do grain conveyor belts have to be static conductive?
Grain handling and storage facilities must use conveying equipment belts made of static conductive materials. Sentence 5.3.3.2 (2) of the National Fire Code of Canada 2020 sets that rule to prevent static charges building up.
What happens if static is not controlled in a dust process?
Uncontrolled static can discharge as a spark strong enough to ignite a dust cloud or a flammable vapour. NFPA presents NFPA 77 as its guidance for preventing the ignition of vapours, dust and particulates by grounding and bonding.
Sources
- National Fire Code of Canada 2020 (opens in a new tab), National Research Council Canada.
- NFPA 77, Recommended Practice on Static Electricity (opens in a new tab), National Fire Protection Association.
- NFPA 660, Standard for Combustible Dusts and Particulate Solids (opens in a new tab), National Fire Protection Association.
- Approved amendments for Part 6, Combustible Dusts, in the Occupational Health and Safety Regulation and the Prevention Manual (opens in a new tab), WorkSafeBC.