Combustible Dust Testing

Which laboratory tests a dust may need, what each one measures, how the results are used, and what BC requires.

Estimate your cost

Would you like to get pricing for the following equipment that will likely be required as a result of your study?

Combustible dust testing sends a sample of your dust to a laboratory to find out whether it can explode, how violently, and how easily it ignites. A simple screen answers the first question; the full results give the engineer the values needed to design explosion protection, set safe oxygen levels and judge ignition sources. The tests chosen depend on the dust, the process and what the results will be used for.

What is combustible dust testing?

Combustible dust testing is laboratory measurement of how a dust behaves as a cloud or a layer: whether it is explosible, how hard and fast it explodes, and the concentration, energy, temperature or oxygen level at which it ignites or stops burning.

BC's amended regulation names ASTM E1226-19, Standard Test Method for Explosibility of Dust Clouds, for its go/no-go screen and ASTM E1515-14 for minimum explosible concentration. The Canadian Centre for Occupational Health and Safety also points out that a sample may need to go to a laboratory for testing.

Which combustible dust tests are there, and what does each measure?

The common combustible dust tests are the go/no-go screen, Kst and Pmax, minimum explosible concentration, minimum ignition energy, minimum ignition temperature and limiting oxidant concentration, and each answers a different design question.

Combustible dust tests: what each measures, where a source names its use, and the method
TestWhat it measuresUsed forMethod
Go/no-go screeningWhether the dust cloud is explosible at allBC deflagrability determination (6.139)ASTM E1226 screening methodology
UN preliminary screening testWhether the dust is ignitableBC ignitability determination (6.138)UN Manual of Tests and Criteria, 33.2.4.3.1
Kst and PmaxThe Kst and Pmax values of the dust cloud, from an explosibility testNot named in the BC regulation or the fire code; the engineer orders it where a design needs itLaboratory method chosen for the dust
MECThe lowest dust concentration in air that can explodeBC deflagrability determination (6.139), as an alternativeASTM E1515
MIEThe minimum ignition energy of a dust cloud in airNot named in the rules covered here; the engineer orders it where the hazard calls for itLaboratory method chosen for the dust
MITThe minimum autoignition temperature of a dust cloud, and the hot-surface ignition temperature of a dust layerNot named in the rules covered here; the engineer orders it where the hazard calls for itLaboratory method chosen for the dust
LOCThe limiting oxygen (oxidant) concentration of a dust cloudOxidant concentration reduction under NFPA 69Laboratory method chosen for the dust

Kst and Pmax testing is not named in BC's regulation or the national fire code; the engineer orders it when explosion protection has to be designed for the dust. NFPA 69's 2024 edition includes an annex on limiting oxidant concentrations.

When is a go/no-go dust test enough?

A go/no-go dust test is enough when the only question is whether a dust is explosible at all, as in BC's deflagrability determination, while explosion protection design needs measured values such as Kst and Pmax.

Section 6.139 of BC's OHS Regulation names two ways to make that determination by test: the go/no-go screening methodology in ASTM E1226-19, or ASTM E1515-14 for minimum explosible concentration, with a similar published test or published objective data as alternatives.

What does BC require for identifying combustible dust?

From January 4, 2027, a BC employer must assume a dust is ignitable and deflagrable unless a written determination, made with a qualified person, shows it is not, using a named screening test, a similar published test or published objective data.

  • Assumption. Section 6.137: ignitable unless shown otherwise under 6.138, and deflagrable unless shown otherwise under 6.139.
  • Ignitability. Section 6.138: the UN preliminary screening test (Manual of Tests and Criteria, seventh edition, 33.2.4.3.1), a similar published screening test, or published objective data.
  • Deflagrability. Section 6.139: the go/no-go screening methodology in ASTM E1226-19, ASTM E1515-14 for minimum explosible concentration, a similar published test, or published objective data.
  • Form. Each determination is in writing and made in consultation with a qualified person.

The is my dust combustible guide walks through the same decision. The results feed the combustion risk assessment that follows for any combustible dust.

How should dust samples be taken?

Dust samples should come from where the process actually makes or collects the dust, so the results describe the material the plant really handles.

Particle size matters to classification too: under the Hazardous Products Regulations (s. 7.17.1), a mixture classed as a flammable solid with 5.0% or more flammable solid by weight and a particle size of 500 µm or less is a Category 1 combustible dust, as is any mixture shown to catch fire or explode when dispersed in air. The engineer or laboratory sets how much sample to send and how to pack and label it.

Who needs combustible dust testing, and when is it required?

A plant needs combustible dust testing when it has to show whether a dust is explosible, as BC requires from January 4, 2027, or when explosion venting or other protection has to be designed and the dust's own values are not yet known.

Dust explosibility testing in Canada is not tied to one national rule: BC names the tests in its regulation, while elsewhere the need usually comes from a dust hazard analysis or from explosion venting design.

How does dust testing differ from a dust hazard analysis?

Dust testing measures the properties of the dust itself in a laboratory, while a dust hazard analysis uses those properties, with the plant's processes and equipment, to find where fire and explosion hazards exist and which safeguards are needed.

Testing often comes first: a DHA can start without results, but it usually adds about 3–6 weeks when a sample still has to go to a laboratory. Once a DHA is done, its open items are worked through under DHA recommendations implementation. Metal and pharmaceutical dusts have their own pages: metal dust and pharmaceutical dust.

What does combustible dust testing cost, and how long does it take?

Combustible dust testing for the dust from one process or collection system starts at $1,500–$4,000 before HST and typically takes 3–6 weeks for laboratory results, depending on the tests needed and the laboratory's queue.

Combustible dust testing$1,500–$4,000Starting range, before HST. The estimator on this page gives a range for your own facility.

The cost page lists every study's starting range.

Combustible dust testing questions

Does the fire code require dust testing?

Dust testing is not named in the national fire code, but test results are one way to show whether its dust section reaches a building at all. Article 5.3.1.1 of the National Fire Code of Canada 2020 sets the scope of that section, Dust-Producing Processes.

Can published data be used instead of testing?

Published data can be used in some cases, but testing the actual dust is preferred once it is available. Sections 6.138 and 6.139 of BC’s OHS Regulation accept published objective data in place of a test, as long as the determination is in writing and made with a qualified person.

Are metal dusts treated differently?

Metal dusts are treated differently in the rules more than in the tests, so their results feed metal-specific requirements. BC’s section 6.154 sets separate metal dust removal rules from January 4, 2027, and NFPA 660 (2025) now holds the former NFPA 484 requirements for combustible metals.

How often should dust be retested?

Dust should be retested when the material, particle size or process changes in a way that could change the results. In BC, a significant change in machinery, equipment or work processes also requires the combustion risk assessment to be updated (section 6.140 (3)), and new dust data feeds that update.

What happens if the dust is never tested in BC?

An untested dust in BC is treated as ignitable and deflagrable from January 4, 2027. Section 6.137 of the OHS Regulation requires the employer to assume both unless a written determination under sections 6.138 and 6.139 shows otherwise.

Sources

  1. Approved amendments for Part 6, Combustible Dusts, in the Occupational Health and Safety Regulation and the Prevention Manual (opens in a new tab), WorkSafeBC.
  2. Hazardous Products Regulations (SOR/2015-17), Subpart 17 Combustible Dusts and Schedule 5 (opens in a new tab), Government of Canada, Justice Laws.
  3. National Fire Code of Canada 2020 (opens in a new tab), National Research Council Canada.
  4. NFPA 69, Standard on Explosion Prevention Systems (opens in a new tab), National Fire Protection Association.
  5. NFPA 660, Standard for Combustible Dusts and Particulate Solids (opens in a new tab), National Fire Protection Association.
  6. OSH Answers: Combustible Dust (opens in a new tab), Canadian Centre for Occupational Health and Safety.