Skip to content
DustHazardAnalysis.ca
Menu

Hazardous Location Classification in Ontario

How the Ontario Electrical Safety Code and ESA treat combustible dust areas, which classification system applies, and who must do the work.

Estimate your cost

Would you like to get pricing for the following equipment that will likely be required as a result of your study?

A hazardous location classification in Ontario follows the Ontario Electrical Safety Code, the Canadian Electrical Code with Ontario amendments, which the Electrical Safety Authority issues and explains in its bulletins. Where combustible dust can form an explosive cloud, the area is classified by zone and every piece of electrical equipment there must be approved and marked for that zone. ESA is clear that a licensed professional engineer does the classification.

What does the Ontario Electrical Safety Code require for dust areas?

The Ontario Electrical Safety Code requires areas where explosive dust may be present to be classified by the nature of the hazard and how likely and lasting it is, with electrical equipment approved and marked for the resulting zone.

  • Adoption. O. Reg. 164/99 adopts CSA C22.1:24 with the Ontario amendments dated June 12, 2024 as the Electrical Safety Code; every act in connection with the use of electricity must comply with it.
  • Classification. Rule 18-004 requires hazardous locations to be classified; Rule 18-002 sets Zone 20, 21 and 22 for dust, by likelihood and duration.
  • Equipment. Rule 18-050 requires equipment approved and marked for its zone; dust-area equipment is dust-tight, excluding dust and tested for heat when blanketed with it.
  • Records. A descriptive system document for intrinsically safe and non-incendive systems, with its calculations, is kept at the facility for its life.

What role does the Electrical Safety Authority play?

The Electrical Safety Authority issues the Ontario amendments to the Canadian Electrical Code, keeps copies of the Electrical Safety Code available to the public, and explains the hazardous location rules in OESC bulletins such as Bulletin 18-1-21.

ESA describes its role as a mandate from the Ontario government to improve public electrical safety. Its Bulletin 18-1-21, issued May 2025, replaces Bulletin 18-1-20 and covers how hazardous locations are classified, which equipment is allowed, and how to find an engineer for area classification.

Which classification system does my Ontario dust area need?

An Ontario dust area with a new electrical installation is classified by zone, while an existing Class or Division installation being modified may keep that system, so four questions settle which one applies.

Zone or Class and Division? 4 questions

  1. Could dust in the area be suspended in the air in explosive concentrations?Yes: Go to question 2.No: The Section 18 dust zones are not needed for that area; the rest of the Ontario Electrical Safety Code still applies.
  2. Is the electrical installation in that area new?Yes: ESA says new installations where explosive dust may be present are classified using the Zone system: Zone 20, 21 or 22.No: Go to question 3.
  3. Was the existing installation classified by Class or Division, and are additions, modifications or renovations now planned for it?Yes: The Class or Division system may continue, using the Class I, II and III requirements in Annex J18 of Appendix J.No: Keep the existing classification and its records current; a change to the process or equipment brings you back to question 2 or 3.
  4. Is every piece of electrical equipment in the area approved and marked for its zone?Yes: That meets Rule 18-050 as ESA describes it; Class/Division-marked equipment may be used in the equivalent zone group under Table 18A.No: Rule 18-050 requires equipment approved and marked as suitable for the zone in which it is used.

Based on the Ontario Electrical Safety Code as explained in ESA Bulletin 18-1-21. The engineer confirms the classification for your site.

When does an Ontario operation count as a dust location?

An Ontario operation counts as a dust location wherever explosive dust concentrations may be present, and ESA's typical examples are grain elevators, flour mills, plants that grind or mix feed, coal pulverizing, and starch or magnesium processing.

For farms, ESA's Table B1 is a guide only, splitting farms that grind or mix feed for their own use from commercial farms, flour mills, alfalfa mills and terminal grain elevators. ESA also notes that good housekeeping and suitable dust collecting systems help keep the hazard low.

How does an Ontario classification differ from a pre-start review?

An Ontario hazardous location classification maps electrical zones under the Electrical Safety Code, while a dust collector pre-start review checks one new or modified collector against Regulation 851 before it runs.

Workers in classified areas are also protected by Regulation 851 section 7, a point ESA's bulletin makes to code users. Collector building rules sit on the Ontario Fire Code dust-producing processes page; how Ontario's rules fit together is on the dust hazard analysis in Ontario page.

How much does hazardous location classification in Ontario cost, and how long does it take?

A hazardous location classification in Ontario covering the dust areas around one process or collector starts at $4,000–$9,000 before HST; the drawings and documents generally take 3–6 weeks from go-ahead, longer where many rooms need zoning.

Hazardous location classification, one process or dust collection system$4,000–$9,000Starting range, before HST. The estimator on this page gives a range for your own facility.

The estimator here opens with Ontario selected; see the hazardous location classification overview, the Alberta version and the cost page.

Ontario hazardous location questions

Which electrical code edition is in force in Ontario?

Ontario’s electrical code in force is the 2024 Ontario Electrical Safety Code, the 29th edition, effective May 1, 2025. O. Reg. 164/99 adopts CSA C22.1:24 together with the Ontario amendments dated June 12, 2024 and issued by the Electrical Safety Authority.

Who must classify a hazardous location in Ontario?

A qualified, licensed professional engineer must classify a hazardous location in Ontario. ESA Bulletin 18-1-21 says so in its section on how to contact an engineer to perform area classification.

Do farms in Ontario need a dust classification?

Ontario farms that handle grain dust can use ESA’s farm table as a guide to wiring and equipment, but only as a guide. ESA Bulletin 18-1-21 says Table B1 may be used only as a guide, and it separates farms making feed for their own use from commercial farms, flour mills and terminal grain elevators.

How often should an Ontario classification be reviewed?

An Ontario classification should be reviewed whenever the electrical installation, the process or the dust changes. ESA Bulletin 18-1-21 sets out which classification system applies to additions, modifications and renovations, and the descriptive system document and calculations stay on file for the life of the facility.

What happens if an Ontario dust area is not classified?

An unclassified Ontario dust area has no basis for the zone-marked equipment the Electrical Safety Code requires. Section 2 of O. Reg. 164/99 requires every act in connection with the use of electricity in Ontario to comply with the Electrical Safety Code, and Rule 18-050 sets the equipment marking.

Sources

  1. O. Reg. 164/99: Electrical Safety Code (opens in a new tab), Government of Ontario, e-Laws.
  2. Ontario Electrical Safety Code (29th edition/2024) (opens in a new tab), Electrical Safety Authority.
  3. OESC Bulletin 18-1-21: Classification of hazardous locations (opens in a new tab), Electrical Safety Authority.
  4. R.R.O. 1990, Reg. 851: Industrial Establishments (sections 7 and 63 to 65) (opens in a new tab), Government of Ontario, e-Laws.