A combustible dust management program in BC is the written plan for keeping your dust from burning or exploding, once an assessment has shown that it can. It explains how each required control is put in place, when equipment and rooms are inspected, and what people do if a control fails or dust catches fire. From January 4, 2027, every BC workplace whose assessment finds a combustion hazard needs one, along with training for the workers exposed.
Do you need a combustible dust management program in BC?
A combustible dust management program is required in BC wherever the combustion risk assessment for a dust finds a combustion hazard, and it comes with instruction and training for the workers who could be exposed.
Section 6.135 links the program to the assessment: once a hazard is identified, the employer must prepare, implement and update the program. If the assessment finds no combustion hazard, no program is required, and the control sections 6.147 to 6.159 do not apply to that employer (section 6.146). Previously, WorkSafeBC combustible dust management program duties applied only to wood dust; from 2027 they cover any combustible dust.
What must a combustible dust management program contain?
A combustible dust management program must describe how each required control is carried out, add any other controls needed, and set inspection schedules and procedures for a failed control or an unintended combustion of dust.
| The program must | Section |
|---|---|
| Describe how the employer will implement the controls required by sections 6.147 to 6.159, as applicable | 6.141 (1) (a) |
| Specify any additional controls needed to minimize combustion risks and how they will be implemented | 6.141 (1) (b) |
| Include schedules and procedures for regular inspections of rooms and buildings, machinery and equipment, and work processes that could give rise to a combustion risk | 6.141 (1) (c) |
| Include procedures for responding to the failure of a control | 6.141 (1) (d) |
| Include procedures for responding to an unintended combustion of dust | 6.141 (1) (e) |
| Be in writing, prepared and updated with a qualified person, and based on the combustion risk assessment and an assessment of the controls already in place | 6.141 (2) |
One person coordinates the program at each workplace, either the employer or an employee who knows the controls and the safe operation of the equipment (section 6.141 (4)). A qualified person reviews the whole program at least once a year (section 6.142).
Is WorkSafeBC's guideline G6.141 final?
As of November 2026, WorkSafeBC's guideline on combustible dust management programs, G6.141, is still a draft posted on August 10, 2026, so a program is built on the regulation itself until the final version is out.
The draft, titled G6.141, Combustible dust management program, was developed to clarify how to establish, implement, maintain and continually improve a program, and feedback was accepted until October 2, 2026. The engineer brings the program into line with the final guideline once it is out.
How are dust housekeeping and ignition sources controlled?
Housekeeping and ignition control take up most of a typical program: the employer sets a maximum dust accumulation, a cleaning schedule and cleaning methods, and removes or controls competent ignition sources wherever combustible dust is generated or handled.
Dust on surfaces (section 6.153)
Where combustible dust could build up on surfaces, the employer must determine with a qualified person, and document, the maximum amount allowed to accumulate, a cleaning schedule that keeps it below that amount, and the cleaning methods. Methods have to minimize both ignition and dust clouds. Compressed air is allowed only with regulated low pressure, ignition sources removed or shut down first, and the blown-down dust cleaned up before work resumes. Metal dust has its own section (6.154), which puts conductive, non-sparking scoops and brooms first.
Ignition sources (section 6.147)
In areas where combustible dust is generated or handled, competent ignition sources must be removed or, if that is not practicable, controlled. That includes friction in equipment exposed to dust, hot work done under written procedures developed with a qualified person, static charge controlled through grounding and bonding, and mobile equipment selected and operated so that it does not become an ignition source.
Building-side rules on ignition, bonding and dust removal also come from the fire code; the BC Fire Code dust-producing processes page sets them against sections 6.147 to 6.159. Two parts of ignition control have their own pages: bonding and grounding and spark detection.
What does a combustible dust management program cost?
A combustible dust management program typically starts at $6,000–$12,000 before HST for one process or dust collection system, for writing the program from an existing combustion risk assessment.
Management program questions
When is a combustible dust management program required?
A combustible dust management program is required when the combustion risk assessment finds a combustion hazard. Section 6.135 (b) (iii) then requires the employer to prepare, implement and update a program for that dust, and to give workers instruction and training on the hazard.
Is there a deadline to have the program in place?
There is no fixed deadline for having the program in place. WorkSafeBC's explanatory notes say section 6.141 does not set a prescribed timeline for when a program must be implemented, because it applies across very different workplaces. The rules themselves take effect on January 4, 2027.
How often does the program have to be reviewed?
The program has to be reviewed in full at least once a year, and in part after certain events. Section 6.142 requires a qualified person to review the entire program at least annually, and to review the relevant parts after the assessment is updated, a control fails or dust combusts unintentionally.
Who is responsible for running the program?
One named person at each workplace is responsible for running the program: the employer or a knowledgeable employee. Section 6.141 (4) requires overall coordination to be assigned to the employer or an employee who knows the controls in the program and the safe operation of the machinery and equipment involved.
Can compressed air still be used to clean up dust?
Compressed air can still be used to clean up dust, but only under three conditions. Section 6.153 (5) requires the air pressure to be regulated and set at the lowest pressure that works, every competent ignition source to be removed or shut down first, and the blown-down dust to be cleaned up before ignition sources are used again.
How does a management program differ from the combustion risk assessment?
The combustion risk assessment finds and rates each combustion hazard, while the combustible dust management program is the written plan of controls that follows when a hazard is found. Section 6.141 (2) requires the program to be based on the combustion risk assessment and on an assessment of the controls already in place.
What happens if a required program is not put in place?
Without a required combustible dust management program, a BC employer whose assessment found a combustion hazard does not meet the amended regulation. Section 6.135 (b) (iii) requires the program and worker training once a hazard is identified, and the control sections 6.147 to 6.159 then apply (section 6.146).
Sources
- Approved amendments for Part 6, Combustible Dusts, in the Occupational Health and Safety Regulation and the Prevention Manual (opens in a new tab), WorkSafeBC.
- G6.141 Combustible dust management program (draft guideline) (opens in a new tab), WorkSafeBC.
- Preparing for regulatory updates (WorkSafe Magazine, Fall 2026) (opens in a new tab), WorkSafeBC.
- Board of Directors decision: Combustible dusts (2025/11/14-07) (opens in a new tab), WorkSafeBC.