A hazardous location classification for combustible dust is an engineer's map of where an explosive dust atmosphere could form in a plant and how likely and how long it would be there. Each area is placed in a zone under the Canadian Electrical Code, so that motors, lights, switches and other electrical equipment there are approved for that zone and cannot ignite the dust. The classification drawing and its documentation stay with the facility.

What is a hazardous location classification?

A hazardous location classification is the documented division of a facility into hazardous areas, by the nature of the hazard and how likely an explosive gas or dust atmosphere is, so electrical equipment can be selected and installed for each area.

For hazardous area classification in Canada the basis is Section 18 of the Canadian Electrical Code, Part I. ESA describes Section 18 as providing "prescriptive requirements for hazardous locations where explosive atmospheres exist", with Rule 18-004 requiring locations to be classified by the nature of the hazard.

How does the Canadian Electrical Code classify dust locations?

Dust locations are classified as Zone 20, Zone 21 or Zone 22 by how likely an explosive dust atmosphere is and how long it lasts, while older installations may still use the Class II hazardous location divisions.

  • Zones 20, 21 and 22. Rule 18-002 defines locations where explosive dust may be present by likelihood and duration as Zone 20, Zone 21 and Zone 22 (ESA, for the Ontario Electrical Safety Code).
  • Class and Division. In Ontario, existing installations classified by Class or Division may keep that system for additions and renovations, using the Class I, II and III rules in Annex J18 of Appendix J.
  • Equipment. Under Rule 18-050, equipment in hazardous locations must be approved and marked as suitable for the zone in which it is used.
  • Typical dust locations. ESA's examples include grain elevators, flour mills, feed grinding and mixing plants, coal pulverizing plants, starch plants and magnesium processing plants.

Who needs a hazardous location classification, when is it required, and who does it?

A facility needs a hazardous location classification wherever combustible dust can form an explosive atmosphere around electrical equipment, and the work is done by a professional engineer, as Alberta's OHS Code and Ontario's Electrical Safety Authority both state.

The fire code points the same way: Section 5.3 of the National Fire Code of Canada 2020 requires cleaning equipment and portable electrical equipment used in combustible dust atmospheres to conform to CSA C22.1. In Alberta, section 162.1 of the OHS Code requires classification by a professional engineer, or a competent person the engineer authorizes, once the hazard assessment finds a hazardous location, with documentation of the boundaries and ignition controls. Plants where solvents and powders meet, such as pharmaceutical and nutraceutical plants, may need gas and dust areas classified together.

Which electrical code edition applies?

As of November 2026, every province in the table applies the 26th edition of the Canadian Electrical Code, CSA C22.1-24: Ontario through its 2024 Ontario Electrical Safety Code with Ontario amendments, and the others by adopting or declaring it in force.

Electrical code edition in force, by province
ProvinceElectrical codeIn forceMore
OntarioOntario Electrical Safety Code, 29th edition (CSA C22.1:24 with Ontario amendments), O. Reg. 164/99May 1, 2025Ontario classification
AlbertaCSA C22.1-24 Canadian Electrical Code, 26th editionApril 1, 2025Alberta classification
British ColumbiaBC Electrical Code: CSA C22.1-24, 26th edition, with no BC deviations (Technical Safety BC)March 4, 2025BC dust rules
Saskatchewan2024 Canadian Electrical Code, enforced by TSASK from June 1, 2025March 1, 2025Saskatchewan dust rules
ManitobaManitoba Electrical Code, Man. Reg. 30/2026: CSA C22.1:24 with a schedule of Manitoba amendmentsApril 1, 2026Manitoba dust rules
New BrunswickCSA C22.1-24, 26th edition, under General Regulation 84-165March 15, 2026New Brunswick dust rules

What does a classification give you?

A hazardous location classification gives you drawings of each classified area and its boundaries, the zone for each, the equipment marking each zone needs and the measures that prevent unintended ignition, all kept on file for the facility.

Alberta's OHS Code requires documentation of the classified boundaries and the measures to prevent ignition. ESA asks for a descriptive system document for intrinsically safe and non-incendive systems, kept with the owner and stored at the facility for its life.

How does a classification differ from a dust hazard analysis?

A hazardous location classification deals with electrical ignition sources and equipment selection by zone, while a dust hazard analysis covers every fire, flash fire and explosion scenario, including collectors, housekeeping and explosion protection.

A DHA can recommend a classification where it finds dust clouds near electrical equipment, and the fire code rules on dust-producing processes are on the combustible dust fire code page. Static from moving powders is a separate ignition source, covered under bonding and grounding for combustible dust.

What does a hazardous location classification cost, and how long does it take?

A hazardous location classification for one dust-producing process or collection system starts at $4,000–$9,000 before HST and typically takes 3–6 weeks from go-ahead, more where a plant has many rooms or processes to map.

Hazardous location classification, one process or dust collection system$4,000–$9,000Starting range, before HST. The estimator on this page gives a range for your own facility.

The cost page lists every study's starting range.

Hazardous location classification questions

Are Class II divisions still used for dust areas?

Class II divisions are still used for some existing installations, but new dust areas are classified by zone. ESA Bulletin 18-1-21 says new installations in Ontario use the Zone system, existing Class or Division installations may keep it when modified, and Alberta’s OHS Code still refers to Class II, Division 1 locations as defined in the Canadian Electrical Code (s. 166 (4)).

Who can classify a hazardous location?

A professional engineer classifies a hazardous location, or in Alberta a competent person the engineer authorizes. Alberta’s OHS Code s. 162.1 (1) sets that rule, and the Electrical Safety Authority says classification in Ontario is required to be done by a qualified, licensed professional engineer.

Is dust-tight equipment the same as explosion-proof?

Dust-tight equipment is not the same as explosion-proof equipment. ESA Bulletin 18-1-21 explains that equipment for dust areas is often called explosion-proof by mistake, but is dust-tight: it excludes dust and is tested for safe heat dissipation when blanketed with dust.

How often should a classification be reviewed?

A hazardous location classification should be reviewed whenever its basis changes, for example new equipment, a new process or a different dust. Alberta’s OHS Code s. 162.1 (2) requires the classification to be reviewed and updated when the hazard assessment shows its basis has changed.

What happens if a dust area is never classified?

Without a classification, there is no basis for choosing electrical equipment marked for the zone, which Rule 18-050 of the Ontario Electrical Safety Code requires in hazardous locations. In Alberta, section 162.1 of the OHS Code makes classification by a professional engineer a duty once the hazard assessment finds a hazardous location.

Sources

  1. OESC Bulletin 18-1-21: Classification of hazardous locations (opens in a new tab), Electrical Safety Authority.
  2. Ontario Electrical Safety Code (29th edition/2024) (opens in a new tab), Electrical Safety Authority.
  3. O. Reg. 164/99: Electrical Safety Code (opens in a new tab), Government of Ontario, e-Laws.
  4. Occupational Health and Safety Code, Part 10: Fire and Explosion Hazards (Alberta Regulation 191/2021) (opens in a new tab), Government of Alberta.
  5. Electrical codes and standards (opens in a new tab), Government of Alberta (Municipal Affairs).
  6. Information Bulletin IB-EL 2024-01: Adoption of BC Electrical Code, 2024 Edition (opens in a new tab), Technical Safety BC.
  7. Electrical (opens in a new tab), Technical Safety Authority of Saskatchewan (TSASK).
  8. Manitoba Electrical Code, Manitoba Regulation 30/2026 (opens in a new tab), Government of Manitoba.
  9. General Regulation 84-165, Electrical Installation and Inspection Act (opens in a new tab), Government of New Brunswick.
  10. National Fire Code of Canada 2020 (opens in a new tab), National Research Council Canada.