Explosion Venting Design and Explosion Protection
How dust equipment is protected against an internal explosion, which method fits which situation, and what the design gives you.
Estimate your cost
Explosion venting design is the engineering that decides how a dust collector, silo or other vessel survives a dust explosion inside it: by venting it to a safe place, suppressing it as it starts, isolating it from connected equipment or containing it. The design sets the method, size and location of each device and the hazard zone around any vent, so the protection matches the dust and the plant layout.
What is explosion venting design?
Explosion venting design is the engineered choice, sizing and placement of vents or other devices that keep a dust deflagration inside equipment from causing critical structural and mechanical damage, which is the aim the national fire code sets for venting.
Under Article 5.3.1.6 of the National Fire Code of Canada 2020, an activity that creates significant concentrations of combustible dust is located only in a building with explosion venting to the outdoors, designed to good engineering practice such as NFPA 68. NFPA describes NFPA 68 as covering the design, location, installation, maintenance and use of devices that vent the combustion gases and pressures of a deflagration within an enclosure.
Which explosion protection methods are there?
The main explosion protection methods for dust equipment are venting, flameless venting, suppression, isolation, containment and keeping the atmosphere from burning, and NFPA 68 and NFPA 69 between them cover how each is designed and maintained.
- Venting. A deflagration vent releases the pressure and flame of an explosion inside equipment to a safe place; NFPA 68 also sets the fireball and hazard distance around the vent.
- Flameless venting. A vent fitted with a flame-arresting device; whether it suits a given vessel and dust is part of the design.
- Suppression. An explosion suppression system detects a deflagration as it starts and discharges suppressant into the equipment (NFPA 69, Chapter 10).
- Isolation. Active isolation uses detection and fast-acting devices, and passive isolation acts without them, to stop a deflagration travelling along ducts (NFPA 69, Chapters 11 and 12).
- Containment. Equipment built strong enough to hold the deflagration pressure (NFPA 69, Chapter 13).
- Prevention. Keeping oxygen below the limiting oxidant concentration, or the dust below a burnable concentration (NFPA 69, Chapters 7 and 8).
Ignition control upstream, such as a spark detection and extinguishing system, is a separate layer that NFPA 69 covers in its own chapter.
Which explosion protection approach fits my equipment?
The right explosion protection approach depends on whether the equipment is indoors or outdoors, whether a vented fireball can be kept away from people, how the equipment connects to others and whether venting can be adequate at all.
| Situation | Approach | Where it is set |
|---|---|---|
| A dust collector over 2.36 m³/s outside the building | Explosion venting to the outdoors, at least 0.1 m² of vent area per m³ of collector volume | NFC 5.3.1.4 (1) |
| A dust collector over 2.36 m³/s inside the building | Venting to the outdoors, an automatic explosion prevention system, or a 1 h fire-separated room vented outdoors | NFC 5.3.1.4 (2) |
| Conditions that prevent adequate explosion venting | An explosion prevention system, designed to practice such as NFPA 69 | NFC 5.3.1.7 |
| Vents that discharge where people may be | Vents pointed away from workers; in BC, vents and their blast areas marked with signs | CCOHS; BC OHS 6.158 |
| Equipment connected by ducts or pipes | Isolation, active or passive, so a deflagration cannot travel to the next vessel | NFPA 69, Ch. 11 and 12; BC OHS 6.140 (2) (c) (ii) |
| Equipment strong enough to hold the deflagration pressure | Pressure containment | NFPA 69, Ch. 13 |
| Keeping the atmosphere from burning at all | Oxidant concentration reduction or combustible concentration reduction | NFPA 69, Ch. 7 and 8 |
The engineer confirms the choice for each vessel from the dust and the layout. Laboratory values for the dust are covered on the combustible dust testing page.
Who needs explosion venting design, and when is it required?
A plant needs explosion venting design when the fire code requires venting or an explosion prevention system, as it does for dust collectors over 2.36 m³/s and activities with significant dust concentrations, or when a DHA recommends protection for a vessel.
Ontario's Fire Code goes further than the national code and requires the venting and prevention systems to conform with NFPA 68 and NFPA 69 outright. In British Columbia, the amended OHS Regulation adds that deflagration relief vents and their blast areas must be marked with signs from January 4, 2027. The combustible dust fire code page sets out the national articles.
What does an explosion protection design give you?
An explosion protection design gives you a documented basis for each protected vessel: the method chosen, device sizes and locations, the hazard zone around vents, the interlocks and shutdowns that go with it, and the inspection and maintenance the devices need.
NFPA 69's contents include process shutdown, system acceptance, procedures following system actuation and recordkeeping, which the design and its handover documents cover for each system.
How does explosion protection design differ from a dust hazard analysis?
A dust hazard analysis finds where fire, flash fire and explosion hazards exist and recommends safeguards, while explosion protection design engineers the specific vents, suppression, isolation or containment that carry out those recommendations.
A DHA often ends with protection recommendations for collectors and silos; putting them in order is covered under DHA recommendations implementation.
What does explosion venting design cost, and how long does it take?
Explosion venting design for one process or dust collection system starts at $6,000–$14,000 before HST and typically takes 4–8 weeks from go-ahead, longer where several vessels or connected ducts need protection.
The devices themselves are priced separately from the design. Every study's starting range is on the cost page.
Explosion protection design questions
Does Ontario require NFPA 68 for explosion venting?
Ontario’s Fire Code makes NFPA 68 mandatory for explosion venting and NFPA 69 mandatory for explosion prevention systems. Its Sentences 5.3.1.6 (2) and 5.3.1.7 (2) say each design is made in conformance with the standard, where the national code says only good engineering practice such as it.
Does a vented dust explosion need a clear zone?
A vented dust explosion sends flame and pressure out of the vent, so the area it can reach has to be kept clear of people. NFPA 68’s 2023 edition combines its fireball and hazard distance requirements for gases and dust, and BC’s section 6.158 requires vent blast areas to be marked from January 4, 2027.
Is explosion isolation needed on every duct?
Explosion isolation is considered wherever a deflagration could spread from one piece of equipment to another through ducts or pipes. Section 6.140 (2) (c) (ii) of BC’s OHS Regulation asks the combustion risk assessment to consider exactly that, and NFPA 69 covers active and passive isolation in Chapters 11 and 12.
How often are explosion protection devices inspected?
Explosion protection devices are inspected on the schedule their standard sets and again after any actuation. NFPA 69 gathers its inspection, testing and maintenance requirements in Chapter 15, including procedures following system actuation and recordkeeping.
What happens if equipment that needs explosion protection has none?
Equipment missing required explosion protection can bring a fire inspector’s order, and a deflagration inside it risks critical structural and mechanical damage. Article 5.3.1.6 (2) of the National Fire Code of Canada 2020 sets venting to prevent exactly that damage.
Sources
- National Fire Code of Canada 2020 (opens in a new tab), National Research Council Canada.
- O. Reg. 213/07: Fire Code (Division B, Section 5.3, Dust Producing Processes) (opens in a new tab), Government of Ontario, e-Laws.
- NFPA 68, Standard on Explosion Protection by Deflagration Venting (opens in a new tab), National Fire Protection Association.
- NFPA 69, Standard on Explosion Prevention Systems (opens in a new tab), National Fire Protection Association.
- Approved amendments for Part 6, Combustible Dusts, in the Occupational Health and Safety Regulation and the Prevention Manual (opens in a new tab), WorkSafeBC.
- OSH Answers: Combustible Dust (opens in a new tab), Canadian Centre for Occupational Health and Safety.