Skip to content
DustHazardAnalysis.ca
Menu

NFPA 660 in Canada

What NFPA's consolidated combustible dust standard changed, and how it fits with Canadian fire codes and workplace rules.

Estimate your cost

Would you like to get pricing for the following equipment that will likely be required as a result of your study?

NFPA 660 Canada questions usually start with one change: in 2025 the National Fire Protection Association folded its combustible dust standards into a single document, NFPA 660, Standard for Combustible Dusts and Particulate Solids. Canadian fire codes and workplace rules were written against the older standards and still name them, so plants and engineers work with both sets of numbers for now.

What did NFPA 660 change?

The structure of NFPA's combustible dust requirements is what NFPA 660 changed, consolidating six earlier standards into one, with the NFPA 652 fundamentals and the industry and commodity standards for food, metals, sulfur, wood and particulate solids in a single 2025 edition.

NFPA's product page also lists what is new in the 2025 edition: requirements to evaluate self-heating, thermal instability, water reactivity and chemical reactivity hazards; more on operational readiness reviews; definitions of management of change and transient releases; more on who is qualified to perform a DHA; and clearer bonding and grounding of housekeeping equipment.

Which old standards does NFPA 660 replace, and where are they still cited in Canada?

Six old standards are replaced by NFPA 660, namely NFPA 652, 61, 484, 654, 655 and 664, and each of those old numbers is still cited somewhere in Canada's fire codes, a provincial guideline or a fire marshal's note.

Standards consolidated into NFPA 660 (2025), as NFPA lists them, and where Canadian documents still cite each
Old standardSubjectStill cited in Canada
NFPA 652Standard on the Fundamentals of Combustible DustOntario pre-start review guideline (Item 5)
NFPA 61Prevention of Fires and Dust Explosions in Agricultural and Food Processing FacilitiesNational Fire Code note A-5.3.1.3.(2)
NFPA 484Standard for Combustible MetalsNational Fire Code note A-5.3.1.3.(2); Ontario pre-start review guideline
NFPA 654Prevention of Fire and Dust Explosions from Combustible Particulate SolidsNational Fire Code note; Ontario guideline; NB Technical Note 2019-01
NFPA 655Standard for Prevention of Sulfur Fires and ExplosionsNational Fire Code note A-5.3.1.3.(2)
NFPA 664Prevention of Fires and Explosions in Wood Processing and Woodworking FacilitiesNational Fire Code 5.3.2.1 (a requirement); Ontario Fire Code 5.3.2.1; NB Technical Note

The table maps documents, not chapters; NFPA's public summary does not list where each old standard sits inside NFPA 660.

Where does NFPA 660 in Canada carry weight?

Canadian plants and engineers use NFPA 660 as a reference they choose to work to, not as law, because none of the provincial rules covered here names it, while the fire codes and guidelines cite the related older standards.

  • Fire codes. The national code requires wood dust exhaust systems to conform with NFPA 664 and points to NFPA 68 and 69 as good engineering practice; its note on dust-collecting systems lists NFPA 61, 484, 654, 655 and 664.
  • Ontario. The Fire Code makes NFPA 68, 69 and 664 conformance mandatory, and the pre-start review guideline lists NFPA 652, 654 and 484 among a reviewer's references.
  • British Columbia. The amended OHS Regulation does not mention NFPA at all; it sets its own assessment and program duties.
  • New Brunswick. The Fire Marshal's technical note relies on NFPA 68, 69, 77, 91, 654 and 664.

What should a plant do about NFPA 660 now?

A plant should keep its existing DHA, frame the next revalidation against NFPA 660, and check its code obligations against the article numbers its province actually cites, which an engineer can do in the same study.

A revalidation is the natural point to make the switch; the DHA revalidation guide covers when one is due. The DHA overview page describes the study, and the combustible dust fire code page lists the code articles. Starting ranges are on the dust hazard analysis cost page.

More plain-language answers are in the combustible dust guides.

NFPA 660 questions

Is NFPA 660 law in Canada?

Canadian law does not make NFPA 660 binding in any province covered here, because none of the provincial codes or regulations names it. Canadian rules still cite the older standards, such as NFPA 664 in Article 5.3.2.1 of the National Fire Code of Canada 2020.

Does a DHA written under NFPA 652 still count?

A DHA written under NFPA 652 still counts as a dust hazard analysis, since NFPA 660 carries the NFPA 652 fundamentals forward. NFPA describes the 2025 edition as consolidating NFPA 652 with five other standards; the next revalidation is a natural point to reframe it.

What is new in NFPA 660’s 2025 edition?

The 2025 edition of NFPA 660 adds requirements to evaluate self-heating, thermal instability, water and chemical reactivity, and more on operational readiness reviews. NFPA’s product page also lists new information on who is qualified to perform a DHA.

Why do Canadian codes still name the old standards?

Canadian codes still name the old standards because they were written against editions that existed before NFPA 660. The National Fire Code of Canada 2020, adopted in most provinces covered here, refers to NFPA 61, 484, 654, 655 and 664 by number.

Sources

  1. NFPA 660, Standard for Combustible Dusts and Particulate Solids (opens in a new tab), National Fire Protection Association.
  2. Combustible Dust Explained (opens in a new tab), National Fire Protection Association.
  3. National Fire Code of Canada 2020 (opens in a new tab), National Research Council Canada.
  4. O. Reg. 213/07: Fire Code (Division B, Section 5.3, Dust Producing Processes) (opens in a new tab), Government of Ontario, e-Laws.
  5. Guideline for pre-start health and safety reviews, Item 5: Dust collectors (opens in a new tab), Government of Ontario.
  6. Technical Note 2019-01: Dust-Producing Processes (opens in a new tab), Office of the Fire Marshal, New Brunswick.
  7. Approved amendments for Part 6, Combustible Dusts, in the Occupational Health and Safety Regulation and the Prevention Manual (opens in a new tab), WorkSafeBC.