Dust Hazard Analysis in Ontario
What Regulation 851 and the Ontario Fire Code require for combustible dust, and when a dust collector needs an engineer's pre-start review.
Estimate your cost
A dust hazard analysis in Ontario often starts with a new or changed dust collector. Ontario's Industrial Establishments Regulation sets where a collector for easily ignitable fine dust may sit, and requires an engineer's pre-start review before such a collector is used when it carries a risk of ignition or explosion. The Ontario Fire Code adds its own rules for dust-producing processes. A DHA looks at the whole plant around those rules: every process, collector and room where dust is made or moved.
Who needs a dust hazard analysis in Ontario?
Ontario factories that make or handle combustible dust are the clearest case, because the Industrial Establishments Regulation and the Ontario Fire Code both set dust rules, and a DHA is the engineering study that checks a plant against them.
Neither Regulation 851 nor the Ontario Fire Code uses the term dust hazard analysis. What they set are duties that a DHA tests one by one: where collectors may be located, how dust processes are isolated and vented, how dust is cleaned up, and when an engineer has to review equipment before it starts. Regulation 851 applies to all industrial establishments, so section 65 reaches combustible dust in Ontario workplaces beyond factories, even though the pre-start review applies only in factories.
What does Regulation 851 require for combustible dust?
Ontario's Industrial Establishments Regulation requires dust processes that could form an explosive mixture to be isolated, ventilated, free of ignition sources and vented, and sets where collectors for easily ignitable fine dust may be located.
- Section 63. A process likely to produce dust that can form an explosive mixture with air is carried out in an area that is isolated from other operations, ventilated so the dust does not reach a hazardous concentration, free of potential ignition sources and provided with explosion venting, with baffles, chokes or dampers where applicable.
- Section 64. Where foreign particles entering equipment could create a dust explosion hazard, the equipment has separators that prevent their entry.
- Section 65 (1). A collector for aluminum, magnesium or other fine dust of an easily ignitable nature is located outdoors, or in a room used only for dust-collecting equipment, behind a dust-tight partition with a fire-resistance rating of at least one hour and with explosion venting to the outdoors.
- Section 65 (2). That rule does not apply to a collector that uses an inert liquid, a woodworking collector of less than 0.47 cubic metres per second (other than for wood flour manufacturing), or a collector that safely contains explosions or resists them with effective venting to the outdoors.
Does the pre-start review apply to my dust collector?
An Ontario pre-start health and safety review is needed when a new or modified dust collector in a factory carries a risk of ignition or explosion that creates an imminent hazard, unless the collector is one that section 65 (2) leaves out.
Does the pre-start review apply to your dust collector? 5 questions
- Is the workplace a factory?Yes: Go to question 2.No: The pre-start review in section 7 of Regulation 851 applies in factories, so it does not apply here; section 65 and the fire code can still apply.
- Is the dust collector new, or being modified with new or changed engineering controls or other measures to meet section 65?Yes: Go to question 3.No: Section 7 (2) does not call for a review, but section 65 still sets where the collector may be located.
- Does using the collector involve a risk of ignition or explosion that creates a condition of imminent hazard to a person’s health or safety?Yes: Go to question 4.No: Item 5 of the Table to section 7 does not apply to the collector.
- Is it a collector that section 65 (2) leaves out: one using an inert liquid, a woodworking collector under 0.47 cubic metres per second (wood flour excepted), or one that safely contains or resists explosions with effective venting to the outdoors?Yes: Ontario’s guideline says a review for Item 5 is not required for that collector.No: An engineer has to carry out a pre-start review before the collector is used; Item 5 has no exemptions.
- Has the review been done, with its measures taken, before start-up?Yes: Give a copy of the report to the joint health and safety committee or representative before use, and keep it for as long as the collector stays (section 7 (7) and (8)).No: The collector may not be operated or used until the review is done and its measures are taken, or written notice of the measures taken is given (section 7 (6)).
The sections are in R.R.O. 1990, Reg. 851, and the out-of-scope collectors are listed in the ministry's pre-start review guideline for Item 5. An engineer confirms the answers for your collector.
Who signs the review, what the sealed report covers and what has to happen before start-up are on the dust collector pre-start health and safety review page.
What does the Ontario Fire Code require for dust-producing processes?
Buildings where combustible dusts create an explosion or fire hazard fall under Section 5.3 of the Ontario Fire Code, with rules for cleaning, dust collection, collector location, bonding, explosion venting to NFPA 68 and explosion prevention systems to NFPA 69.
- 5.3.1.4 A dust collector larger than 2.36 m³/s goes outside the building with explosion venting to the outdoors, or inside only with outdoor venting, an automatic explosion prevention system, or a 1 h fire-separated room used only for dust collection.
- 5.3.1.6 and 5.3.1.7 Explosion venting designed in conformance with NFPA 68, and an explosion prevention system in conformance with NFPA 69 where venting is not adequate.
- 5.3.2.1 Woodworking machines that produce dust have a blower and exhaust system installed in conformance with NFPA 664; systems that met the Code on December 31, 2025 and still do are deemed to comply.
Section 5.3 in full, with the points where Ontario's wording differs from the national code, is on the Ontario Fire Code dust-producing processes page.
Who enforces combustible dust rules in Ontario?
Ontario's Ministry of Labour, Immigration, Training and Skills Development inspects workplaces for compliance with the Occupational Health and Safety Act and its Industrial Establishments Regulation, and the Ontario Fire Code is made under the Fire Protection and Prevention Act, 1997.
In practice the question of a DHA comes up at three points: a ministry inspection or the pre-start review for a collector, a fire inspection under the Fire Code, or a property insurer's own requirements. Insurers set those in your policy, so ask yours directly what it expects.
How does a DHA differ from a pre-start review?
An Ontario pre-start review checks a new or modified dust collector against section 65 before it is used, while a DHA looks at every dust process, collector and room for fire, flash fire and explosion hazards and the safeguards each one needs.
The dust collector pre-start review page sets out the review itself, and the electrical zoning of dust areas is on the hazardous location classification in Ontario page.
| Study | Purpose | What triggers it | Who prepares it | Typical output | Starting range |
|---|---|---|---|---|---|
| Dust hazard analysis (DHA) | Identify and evaluate fire, flash fire and explosion hazards, and the safeguards for each | Combustible dust may be present in a process or facility compartment; reviewed at least every five years (NFPA 652) | An engineer; on this site, a professional engineer licensed in the facility’s province | A report listing each hazard, the safeguards in place, recommended safeguards and a plan to put them in | $8,000–$15,000 |
| Ontario dust collector pre-start review | Review a dust collector before it goes into use (Regulation 851, section 7) | A new or modified dust collector in a factory whose use involves a risk of ignition or explosion | An engineer | The engineer’s pre-start health and safety review, completed before the collector is used | $3,500–$7,000 |
| Combustible dust testing | Measure whether a dust cloud can explode and how violently (go/no-go screen, Kst and Pmax) | Test data for the dust is missing, or a BC employer wants to show a dust is not combustible | A dust testing laboratory, from representative samples taken at the plant | Laboratory results: the screening result, and Kst and Pmax values where they are measured | $1,500–$4,000 |
What does a dust hazard analysis cost in Ontario, and how long does it take?
For one dust-producing process or dust collection system, a dust hazard analysis in Ontario starts at $8,000–$15,000 before HST; allow about 4–8 weeks from go-ahead to the final report, and another 3–6 weeks if the dust goes to a laboratory.
How long it takes depends on the number of processes and on any dust testing still needed, and the engineer sets the schedule in the quote. Ontario and a dust hazard analysis are preselected in the estimator here; a collector's pre-start review is a separate quote.
Which Ontario operations do these rules name?
Ontario's own rules name aluminum and magnesium dust, woodworking and wood flour, foundries and grain handling and storage, so those operations are the clearest candidates for a dust hazard analysis in Ontario.
Section 65 of Regulation 851 names aluminum, magnesium and wood flour; the Fire Code has separate subsections for woodworking operations and for grain handling and storage facilities; and Regulation 851 defines foundries to include dust-causing operations around casting. The wood, metal and food and grain pages on the industries list cover these operations.
Ontario combustible dust questions
Does every dust collector in Ontario need a pre-start review?
Not every dust collector in Ontario needs one: the review applies to a new or modified collector in a factory whose use involves a risk of ignition or explosion. Item 5 of the Table to section 7 of Regulation 851 sets that trigger, and the ministry guideline leaves out the collectors described in section 65 (2), such as one that uses an inert liquid.
Who can do a pre-start review for a dust collector?
Only an engineer can carry out the pre-start review for a dust collector in Ontario. Section 7 (4) of Regulation 851 requires an engineer for item 5, and section 7 (5) requires the written report to be signed, dated and sealed under the Professional Engineers Act.
Is NFPA 652 required in Ontario?
Ontario does not write NFPA 652 into its regulation or fire code, though its pre-start review guideline lists it among standards a reviewer should or may use. The Ontario Fire Code itself requires explosion venting designed in conformance with NFPA 68 and explosion prevention systems in conformance with NFPA 69 (Sentences 5.3.1.6 (2) and 5.3.1.7 (2)).
How often should an Ontario DHA be redone?
An Ontario DHA should be redone at least every five years, the cycle NFPA 652 sets, and whenever a dust process or collector is added or changed. A new or modified collector with an ignition or explosion risk also needs its own pre-start review under section 7 of Regulation 851.
What happens if a collector starts up without its review?
A collector that needs a pre-start review may not be operated in Ontario until the review is done and its measures are taken or written notice is given. Section 7 (6) of Regulation 851 sets that rule, and section 7 (7) requires a copy of the report to go to the joint health and safety committee or representative before start-up.
Sources
- R.R.O. 1990, Reg. 851: Industrial Establishments (sections 7 and 63 to 65) (opens in a new tab), Government of Ontario, e-Laws.
- Guideline for pre-start health and safety reviews, Item 5: Dust collectors (opens in a new tab), Government of Ontario.
- O. Reg. 213/07: Fire Code (Division B, Section 5.3, Dust Producing Processes) (opens in a new tab), Government of Ontario, e-Laws.
- Ministry of Labour, Immigration, Training and Skills Development (opens in a new tab), Government of Ontario.
- NFPA 652, Combustible Dust Awareness and Hazard Evaluation (online training series) (opens in a new tab), National Fire Protection Association.